J+J Automation UK Limited

R20 Basic On-Off JJ Electric Actuator

R20 Basic On-Off JJ Electric Actuator

Basic On-Off Electric Actuator Model RC-20 12V :

  • Overview - Maximum 25Nm basic on-off reversible IP67 12VDC electric quarter turn valve actuator. Manual override. External Din plug connection. Local dome style visual position indicator.Internal fuses. F03, F04 & F05 x 14mm female star mounting.
  • Function - Power open, power close. Stays put on external power failure. Designed to have power on at all times.
  • Sizing Criteria - Max break torque 25Nm. Max run and reseat torque 20Nm. Max ambient temp range -20 to +70C.
  • Options - Heater, 9 opr 11mm female star drive output


Basic On-Off Electric Actuator Model RC-20 110V :

  • Overview - Maximum 25Nm basic on-off reversible IP67 110VAC electric quarter turn valve actuator. Manual override. External Din plug connection. Local dome style visual position indicator.Internal fuses.F03, F04 & F05 x 14mm female star mounting.
  • Function - Power open, power close. Stays put on external power failure. Designed to have power on at all times.
  • Sizing Criteria - Max break torque 25Nm. Max run and reseat torque 20Nm. Max ambient temp range -20 to +70C.
  • Options - Heater.


Basic On-Off Electric Actuator Model RC-20 240V :

  • Overview - Maximum 25Nm basic on-off reversible IP67 240VC electric quarter turn valve actuator. Manual override. External Din plug connection. Local dome style visual position indicator.Internal fuses.F03, F04 & F05 x 14mm female star mounting.
  • Function - Power open, power close. Stays put on external power failure. Designed to have power on at all times.
  • Sizing Criteria - Max break torque 25Nm. Max run and reseat torque 20Nm. Max ambient temp range -20 to +70C.
  • Options - Heater.


Basic On-Off Electric Actuator Model RC-20 24V :

  • Overview - Maximum 25Nm basic on-off reversible IP67 24V electric quarter turn valve actuator. Manual override. External Din plug connection. Local dome style visual position indicator.Internal fuses.F03, F04 & F05 x 14mm female star mounting.
  • Function - Power open, power close. Stays put on external power failure. Designed to have power on at all times.
  • Sizing Criteria - Max break torque 25Nm. Max run and reseat torque 20Nm. Max ambient temp range -20 to +70C.
  • Options - Heater.