J+J Automation UK Limited

J3-H 110-240V Smart Electric Valve Actuator

J3-H 110-240V Smart Electric Valve Actuator

J3-H20 110-240V Max 25Nm Model J3H20 On Off :

  • Overview - Maximum 25Nm 85-240V Multi-voltage reversible IP65 on-off quarter turn smart electric actuator, with manual override, heater, torque limiter, LED status light, external Din plug connection and dome visual indicator. F03,F04 & F05 x 14mm female star mounting.
  • Function - Power open, power close. Stays put on external power failure. Designed to have power on at all times.
  • Sizing Criteria - Max break torque 25Nm. Max run and reseat torque 20Nm. Max ambient temp range -20 to +70C.
  • Options - Failsafe using internal battery (BSR) kit. Modulating using potentiometer positioner (DPS) kit. Failsafe modulating using BSR & DPS kits. 9mm or 11mm female star drive output.


J3-H20BSR 110-240V Max 25Nm Model J3H20 Failsafe :

  • Overview - Maximum 25Nm 85-240V Multi-voltage reversible IP65 failsafe quarter turn smart electric actuator, with manual override, heater, torque limiter, LED status light, external Din plug connection and dome visual indicator. F03,F04 & F05 x 14mm female star mounting.
  • Function - Power open, power close. Fails to pre-set position (open, or close) on external power failure. Designed to have power on at all times. Supplied with BSR (Battery 'Spring Return') failsafe system pre-installed and function tested.
  • Sizing Criteria - Max break torque 25Nm. Max run and reseat torque 20Nm. Max ambient temp range -20 to +70C.
  • Options - DPS Modulating function conversion kit to create failsafe modulating function. 9mm or 11mm female star drive output.


J3-H20DPS 110-240V Max 25Nm Model J3H20 Modulating :

  • Overview - Maximum 25Nm 85-240V Multi-voltage reversible IP65 modulating quarter turn smart electric actuator, with manual override, heater, torque limiter, LED status light, external Din plug connection and dome visual indicator.
  • Function - Continuous external power, movement controlled by DPS (Digital Positioning System) input control signal, typically 4-20mA or 0-10V. Configurable to open, close, or freeze on loss of control signal. Pre-set to fail open, or close on loss of external power failure. Output signal provided. Supplied with DPS system pre-installed and function tested.
  • Sizing Criteria - Max break torque 25Nm. Max run and reseat torque 20Nm. Max ambient temp range -20 to +70C.
  • Options - BSR Failsafe function conversion kit to create failsafe modulating function.


  • 20Nm J3-H 110-240V Smart Electric Valve Actuator

  • 35Nm J3-H 110-240V Smart Electric Valve Actuator

  • 55Nm J3-H 110-240V Smart Electric Valve Actuator

  • 85Nm J3-H 110-240V Smart Electric Valve Actuator